Backflow assembly test: 6938 Sycamore Dr

Approved

Filed Dec 2, 2023 by Jordan Wexler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 2, 2023
Assembly type
DC
Serial number
B628646
Size
3/4
Test gauge serial
G-5119
Gauge calibration date
Apr 8, 2023
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-52-01121
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6938 Sycamore Dr
Owner: Casey Wexler
Parcel 075-52-01121