Back to the backflow review queue

Backflow assembly test: Main Street Medical Offices

Approved

Filed Feb 6, 2025 by Jamie Vance, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 6, 2025
Assembly type
RP
Serial number
W828280
Size
1 1/2
Test gauge serial
G-8372
Gauge calibration date
Aug 27, 2024
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Vance, current on the service date
  • All required fields present
  • Address matches parcel 075-42-01191
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6933 Laurel Rd
Owner: Brandt Holdings LLC
Parcel 075-42-01191