Backflow assembly test: 8233 Cedar Hollow Ln

Approved

Filed Oct 28, 2025 by Jordan Wexler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 28, 2025
Assembly type
DC
Serial number
B118315
Size
3/4
Test gauge serial
G-3783
Gauge calibration date
Jan 30, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-27-01250
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.