Backflow assembly test: 3850 Sycamore Way
ApprovedFiled May 3, 2026 by Jamie Vance, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 3, 2026
- Assembly type
- DC
- Serial number
- Z443208
- Size
- 1
- Test gauge serial
- G-2106
- Gauge calibration date
- Mar 4, 2026
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Vance, current on the service date
- All required fields present
- Address matches parcel 075-35-01163
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.