Back to the backflow review queue

Backflow assembly test: 7609 Orchard Way

Approved

Filed Apr 22, 2026 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Apr 22, 2026
Assembly type
PVB
Serial number
B242035
Size
1
Test gauge serial
G-2129
Gauge calibration date
Feb 26, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-85-01006
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7609 Orchard Way
Owner: Avery Lindqvist
Parcel 075-85-01006