Back to the backflow review queue

Backflow assembly test: 9449 Pine Knoll Ln

Approved

Filed Sep 26, 2025 by Jamie Vance, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 26, 2025
Assembly type
RP
Serial number
A176515
Size
3/4
Test gauge serial
G-7648
Gauge calibration date
Jan 30, 2025
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Vance, current on the service date
  • All required fields present
  • Address matches parcel 075-10-01325
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9449 Pine Knoll Ln
Owner: Morgan Lindqvist
Parcel 075-10-01325