Back to the backflow review queue

Backflow assembly test: 1261 Old Church Trl

Approved

Filed Jul 21, 2026 by Blake Pruitt, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 21, 2026
Assembly type
PVB
Serial number
B852342
Size
1
Test gauge serial
G-9398
Gauge calibration date
Jan 23, 2026
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 075-99-01058
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1261 Old Church Trl
Owner: Riley Marsh
Parcel 075-99-01058