Back to the backflow review queue
Backflow assembly test: Riverside Diner
ApprovedFiled Apr 30, 2026 by Jordan Wexler, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 30, 2026
- Assembly type
- RP
- Serial number
- W795443
- Size
- 1 1/2
- Test gauge serial
- G-1296
- Gauge calibration date
- Mar 24, 2026
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Wexler, current on the service date
- All required fields present
- Address matches parcel 075-39-01320
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3400 Old Church Rd
Owner: Marsh Holdings LLC
Parcel 075-39-01320