Backflow assembly test: 525 Fox Run Way

Approved

Filed Mar 6, 2026 by Alex Fairley, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 6, 2026
Assembly type
RP
Serial number
W348123
Size
3/4
Test gauge serial
G-6599
Gauge calibration date
Dec 14, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Fairley, current on the service date
  • All required fields present
  • Address matches parcel 077-92-01252
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

525 Fox Run Way
Owner: Taylor Fairley
Parcel 077-92-01252