Back to the backflow review queue

Backflow assembly test: Golden Taqueria

Approved

Filed Nov 25, 2023 by Casey Lindqvist, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 25, 2023
Assembly type
RP
Serial number
B794106
Size
2
Test gauge serial
G-2352
Gauge calibration date
Apr 28, 2023
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 077-18-01141
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5721 Pine Knoll Dr
Owner: Kessler Holdings LLC
Parcel 077-18-01141