Backflow assembly test: Golden Taqueria
ApprovedFiled Nov 5, 2024 by Alex Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 5, 2024
- Assembly type
- RP
- Serial number
- B794106
- Size
- 2
- Test gauge serial
- G-8893
- Gauge calibration date
- Sep 18, 2024
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Fairley, current on the service date
- All required fields present
- Address matches parcel 077-18-01141
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.