Backflow assembly test: Golden Taqueria
ApprovedFiled Dec 7, 2025 by Alex Fairley, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 7, 2025
- Assembly type
- RP
- Serial number
- B794106
- Size
- 2
- Test gauge serial
- G-2845
- Gauge calibration date
- Aug 2, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Fairley, current on the service date
- All required fields present
- Address matches parcel 077-18-01141
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.