Back to the backflow review queue
Backflow assembly test: 5440 Pine Knoll Rd
ApprovedFiled Mar 14, 2026 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 14, 2026
- Assembly type
- DC
- Serial number
- K676797
- Size
- 1
- Test gauge serial
- G-6356
- Gauge calibration date
- Oct 5, 2025
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Hollins, current on the service date
- All required fields present
- Address matches parcel 077-49-01054
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5440 Pine Knoll Rd
Owner: Blake Vance
Parcel 077-49-01054