Backflow assembly test: Blue Heron Self Storage
ApprovedFiled Apr 7, 2026 by Blake Hollins, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Apr 7, 2026
- Assembly type
- RP
- Serial number
- A792074
- Size
- 4
- Test gauge serial
- G-2342
- Gauge calibration date
- Oct 7, 2025
- Check valve 1
- 8.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Hollins, current on the service date
- All required fields present
- Address matches parcel 077-26-01197
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4665 Spring Branch Trl
Owner: Ramirez Holdings LLC
Parcel 077-26-01197