Back to the backflow review queue

Backflow assembly test: 5322 Laurel Trl

Approved

Filed Mar 19, 2025 by Morgan Calloway, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 19, 2025
Assembly type
RP
Serial number
A693171
Size
3/4
Test gauge serial
G-1125
Gauge calibration date
Dec 8, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 077-15-01329
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5322 Laurel Trl
Owner: Taylor Okafor
Parcel 077-15-01329