Backflow assembly test: 7300 Hickory Ct

Approved

Filed Jul 10, 2025 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jul 10, 2025
Assembly type
RP
Serial number
K970266
Size
3/4
Test gauge serial
G-2327
Gauge calibration date
Mar 1, 2025
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Hollins, current on the service date
  • All required fields present
  • Address matches parcel 077-30-01340
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7300 Hickory Ct
Owner: Morgan Pruitt
Parcel 077-30-01340