Backflow assembly test: 7397 Laurel Dr

Approved

Filed Jan 20, 2026 by Blake Hollins, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 20, 2026
Assembly type
RP
Serial number
Z409605
Size
3/4
Test gauge serial
G-6736
Gauge calibration date
Jun 17, 2025
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
2.8 psid
Relief valve opened at
3.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Hollins, current on the service date
  • All required fields present
  • Address matches parcel 077-51-01078
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.