Back to the backflow review queue

Backflow assembly test: 5839 Ridgeview Rd

Approved

Filed Dec 1, 2025 by Alex Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Dec 1, 2025
Assembly type
DC
Serial number
Z756495
Size
1
Test gauge serial
G-3535
Gauge calibration date
Jun 24, 2025
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Fairley, current on the service date
  • All required fields present
  • Address matches parcel 077-61-01225
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5839 Ridgeview Rd
Owner: Jamie Marsh
Parcel 077-61-01225