Backflow assembly test: 3191 Meadow Lark Ln

Approved

Filed Oct 6, 2025 by Blake Hollins, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Oct 6, 2025
Assembly type
DC
Serial number
W485407
Size
3/4
Test gauge serial
G-5950
Gauge calibration date
Jun 13, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Hollins, current on the service date
  • All required fields present
  • Address matches parcel 077-81-01147
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3191 Meadow Lark Ln
Owner: Morgan Brandt
Parcel 077-81-01147