Backflow assembly test: Blue Heron Medical Offices
ApprovedFiled Aug 3, 2026 by Morgan Calloway, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 3, 2026
- Assembly type
- RP
- Serial number
- W295365
- Size
- 1 1/2
- Test gauge serial
- G-5964
- Gauge calibration date
- Dec 11, 2025
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Calloway, current on the service date
- All required fields present
- Address matches parcel 077-38-01075
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8694 Quarry Rd
Owner: Danner Holdings LLC
Parcel 077-38-01075