Backflow assembly test: 925 Meadow Lark Way
ApprovedFiled Nov 7, 2025 by Blake Hollins, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 7, 2025
- Assembly type
- RP
- Serial number
- B305288
- Size
- 3/4
- Test gauge serial
- G-9570
- Gauge calibration date
- Sep 18, 2025
- Check valve 1
- 3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Hollins, current on the service date
- All required fields present
- Address matches parcel 077-17-01114
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.