Back to the backflow review queue

Backflow assembly test: 7125 Old Church Ln

Approved

Filed Jul 3, 2025 by Morgan Calloway, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 3, 2025
Assembly type
RP
Serial number
K823097
Size
1
Test gauge serial
G-5206
Gauge calibration date
Apr 25, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 077-64-01332
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7125 Old Church Ln
Owner: Parker Ellery
Parcel 077-64-01332