Backflow assembly test: 6810 Quarry Way

Approved

Filed Sep 9, 2024 by Alex Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Sep 9, 2024
Assembly type
DC
Serial number
Z884103
Size
1
Test gauge serial
G-4584
Gauge calibration date
Jun 10, 2024
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Fairley, current on the service date
  • All required fields present
  • Address matches parcel 077-71-01204
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6810 Quarry Way
Owner: Emerson Ellery
Parcel 077-71-01204