Back to the backflow review queue

Backflow assembly test: 8431 Sycamore Ln

Approved

Filed Aug 23, 2024 by Sam Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 23, 2024
Assembly type
RP
Serial number
A257300
Size
3/4
Test gauge serial
G-6941
Gauge calibration date
Mar 9, 2024
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 079-60-01142
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8431 Sycamore Ln
Owner: Logan Wexler
Parcel 079-60-01142