Backflow assembly test: 4152 Pine Knoll Rd

Approved

Filed Aug 15, 2026 by Parker Nguyen, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 15, 2026
Assembly type
RP
Serial number
K700801
Size
3/4
Test gauge serial
G-9647
Gauge calibration date
Mar 3, 2026
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 079-74-01306
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4152 Pine Knoll Rd
Owner: Hayden Brandt
Parcel 079-74-01306