Backflow assembly test: 1545 Mill Creek Ln
ApprovedFiled Aug 26, 2025 by Parker Okafor, Summit Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 26, 2025
- Assembly type
- RP
- Serial number
- A485473
- Size
- 3/4
- Test gauge serial
- G-4752
- Gauge calibration date
- Feb 12, 2025
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-21-01178
- Readings in range, no flags
- Result: passing. Next due date resets when approved.