Back to the backflow review queue
Backflow assembly test: Crossroads Medical Offices
ApprovedFiled Apr 2, 2025 by Sam Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Apr 2, 2025
- Assembly type
- DC
- Serial number
- A306692
- Size
- 2
- Test gauge serial
- G-5550
- Gauge calibration date
- Jul 2, 2024
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Vance, current on the service date
- All required fields present
- Address matches parcel 079-45-01335
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8057 Old Church Dr
Owner: Ellery Holdings LLC
Parcel 079-45-01335