Backflow assembly test: Crossroads Medical Offices
ApprovedFiled Apr 30, 2026 by Sam Vance, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Apr 30, 2026
- Assembly type
- DC
- Serial number
- A306692
- Size
- 2
- Test gauge serial
- G-5458
- Gauge calibration date
- Jan 8, 2026
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Vance, current on the service date
- All required fields present
- Address matches parcel 079-45-01335
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.