Backflow assembly test: 224 Pine Knoll Trl

Approved

Filed May 30, 2026 by Parker Okafor, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 30, 2026
Assembly type
RP
Serial number
Z867518
Size
1
Test gauge serial
G-1219
Gauge calibration date
Feb 25, 2026
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-69-01121
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

224 Pine Knoll Trl
Owner: Quinn Ramirez
Parcel 079-69-01121