Back to the backflow review queue

Backflow assembly test: Corner Market

Filed Nov 20, 2026 by Reese Danner, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 20, 2026
Assembly type
RP
Serial number
W871311
Size
4
Test gauge serial
G-7031
Gauge calibration date
Feb 25, 2026
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 079-61-01279
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

8463 Hickory Dr
Owner: Pruitt Holdings LLC
Parcel 079-61-01279