Backflow assembly test: Crossroads Grill
ApprovedFiled May 19, 2024 by Parker Okafor, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- May 19, 2024
- Assembly type
- RP
- Serial number
- K756640
- Size
- 2
- Test gauge serial
- G-1361
- Gauge calibration date
- Feb 8, 2023
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-10-01112
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.