Backflow assembly test: 9181 Mill Creek Rd

Approved

Filed Sep 4, 2026 by Parker Okafor, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Sep 4, 2026
Assembly type
DC
Serial number
W688032
Size
1
Test gauge serial
G-6148
Gauge calibration date
Aug 5, 2026
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-93-01049
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.