Back to the backflow review queue

Backflow assembly test: 9139 Ridgeview Way

Approved

Filed Apr 1, 2025 by Cameron Lindqvist, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 1, 2025
Assembly type
DC
Serial number
Z408733
Size
1
Test gauge serial
G-6629
Gauge calibration date
Nov 11, 2024
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 079-59-01120
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9139 Ridgeview Way
Owner: Taylor Lindqvist
Parcel 079-59-01120