Back to the backflow review queue
Backflow assembly test: Crossroads Self Storage
ApprovedFiled Jun 4, 2024 by Parker Nguyen, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jun 4, 2024
- Assembly type
- RP
- Serial number
- Z430859
- Size
- 1
- Test gauge serial
- G-2131
- Gauge calibration date
- Apr 1, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 079-45-01165
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6720 Meadow Lark Way
Owner: Lindqvist Holdings LLC
Parcel 079-45-01165