Back to the backflow review queue

Backflow assembly test: 6253 Laurel Ct

Approved

Filed Jan 3, 2026 by Parker Okafor, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jan 3, 2026
Assembly type
RP
Serial number
W965746
Size
1
Test gauge serial
G-7893
Gauge calibration date
Oct 3, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-53-01096
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6253 Laurel Ct
Owner: Casey Pruitt
Parcel 079-53-01096