Backflow assembly test: Riverside Pizza

Approved

Filed Aug 14, 2026 by Parker Okafor, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Aug 14, 2026
Assembly type
RP
Serial number
W243056
Size
4
Test gauge serial
G-4407
Gauge calibration date
May 26, 2026
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-87-01082
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5811 Ridgeview Way
Owner: Ramirez Holdings LLC
Parcel 079-87-01082