Backflow assembly test: Maple Leaf Diner

Approved

Filed Aug 10, 2025 by Sam Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Aug 10, 2025
Assembly type
RP
Serial number
Z771893
Size
1 1/2
Test gauge serial
G-3493
Gauge calibration date
Jun 19, 2025
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 079-17-01208
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1854 Fox Run Dr
Owner: Harlow Holdings LLC
Parcel 079-17-01208