Backflow assembly test: 4770 Mill Creek Way

Filed Nov 21, 2026 by Parker Okafor, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Nov 21, 2026
Assembly type
RP
Serial number
B741352
Size
1
Test gauge serial
G-2529
Gauge calibration date
Sep 22, 2026
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-12-01073
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.