Back to the backflow review queue
Backflow assembly test: 2287 Turkey Hill Rd
ApprovedFiled Jul 3, 2024 by Cameron Lindqvist, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 3, 2024
- Assembly type
- DC
- Serial number
- B657808
- Size
- 3/4
- Test gauge serial
- G-6345
- Gauge calibration date
- Jan 3, 2024
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Lindqvist, current on the service date
- All required fields present
- Address matches parcel 079-81-01350
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2287 Turkey Hill Rd
Owner: Jordan Danner
Parcel 079-81-01350