Backflow assembly test: 2287 Turkey Hill Rd

Approved

Filed Aug 6, 2025 by Parker Okafor, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Aug 6, 2025
Assembly type
DC
Serial number
B657808
Size
3/4
Test gauge serial
G-9423
Gauge calibration date
Apr 2, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 079-81-01350
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.