Backflow assembly test: Golden Grill

Approved

Filed Sep 28, 2024 by Cameron Lindqvist, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 28, 2024
Assembly type
RP
Serial number
A417983
Size
1 1/2
Test gauge serial
G-9452
Gauge calibration date
Dec 15, 2023
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 079-29-01303
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.