Backflow assembly test: 1894 Ridgeview Dr

Approved

Filed May 11, 2026 by Sam Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
May 11, 2026
Assembly type
RP
Serial number
W481118
Size
1
Test gauge serial
G-2438
Gauge calibration date
Oct 30, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Vance, current on the service date
  • All required fields present
  • Address matches parcel 079-80-01251
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1894 Ridgeview Dr
Owner: Quinn Harlow
Parcel 079-80-01251