Backflow assembly test: 5857 Hickory Trl

Approved

Filed Jul 27, 2026 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 27, 2026
Assembly type
DC
Serial number
B982122
Size
1
Test gauge serial
G-8301
Gauge calibration date
Feb 25, 2026
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Ellery, current on the service date
  • All required fields present
  • Address matches parcel 083-98-01236
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.