Backflow assembly test: 1207 Mill Creek Trl

Approved

Filed Nov 7, 2026 by Reese Kessler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 7, 2026
Assembly type
RP
Serial number
B962321
Size
1
Test gauge serial
G-4140
Gauge calibration date
Nov 1, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Kessler, current on the service date
  • All required fields present
  • Address matches parcel 083-64-01114
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1207 Mill Creek Trl
Owner: Reese Nguyen
Parcel 083-64-01114