Back to the backflow review queue

Backflow assembly test: 1383 Pine Knoll Ln

Approved

Filed Nov 25, 2025 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 25, 2025
Assembly type
RP
Serial number
B829104
Size
1
Test gauge serial
G-7003
Gauge calibration date
Jun 28, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Ellery, current on the service date
  • All required fields present
  • Address matches parcel 083-66-01279
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1383 Pine Knoll Ln
Owner: Blake Kessler
Parcel 083-66-01279