Back to the backflow review queue

Backflow assembly test: Station Bakery

Approved

Filed Jul 28, 2025 by Jordan Fairley, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jul 28, 2025
Assembly type
RP
Serial number
K506361
Size
1 1/2
Test gauge serial
G-4331
Gauge calibration date
Oct 23, 2024
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Fairley, current on the service date
  • All required fields present
  • Address matches parcel 083-97-01171
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3786 Meadow Lark Ln
Owner: Fairley Holdings LLC
Parcel 083-97-01171