Back to the backflow review queue

Backflow assembly test: 2293 Fox Run Ln

Approved

Filed Jul 8, 2026 by Casey Hollins, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 8, 2026
Assembly type
DC
Serial number
A670329
Size
1
Test gauge serial
G-8979
Gauge calibration date
Mar 9, 2026
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Hollins, current on the service date
  • All required fields present
  • Address matches parcel 083-91-01291
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2293 Fox Run Ln
Owner: Hayden Calloway
Parcel 083-91-01291