Backflow assembly test: 8334 Pine Knoll Ln

Approved

Filed Jan 3, 2026 by Casey Ellery, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 3, 2026
Assembly type
RP
Serial number
B752599
Size
1
Test gauge serial
G-3570
Gauge calibration date
May 5, 2025
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Ellery, current on the service date
  • All required fields present
  • Address matches parcel 083-50-01192
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8334 Pine Knoll Ln
Owner: Quinn Danner
Parcel 083-50-01192