Backflow assembly test: Maple Leaf Apartments
ApprovedFiled Nov 7, 2026 by Jordan Fairley, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 7, 2026
- Assembly type
- RP
- Serial number
- K297106
- Size
- 2
- Test gauge serial
- G-3093
- Gauge calibration date
- Jun 25, 2026
- Check valve 1
- 5.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Fairley, current on the service date
- All required fields present
- Address matches parcel 083-54-01099
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2706 Ridgeview Ln
Owner: Wexler Holdings LLC
Parcel 083-54-01099