Backflow assembly test: Crossroads Pizza

Approved

Filed Oct 26, 2024 by Casey Ellery, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 26, 2024
Assembly type
RP
Serial number
K634526
Size
4
Test gauge serial
G-8851
Gauge calibration date
Aug 19, 2024
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Ellery, current on the service date
  • All required fields present
  • Address matches parcel 083-17-01250
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7464 Turkey Hill Way
Owner: Stroud Holdings LLC
Parcel 083-17-01250